general@tekab.com.
Thursday, April 3rd, 2025
Size | : |
|
||
Specification | : | Generally to BS 5308 part-2 |
Conductor | : | Annealed bare/tinned stranded copper |
Insulation (see note) | : | PVC type TI1 to BS 7655 |
Identification | : | Numbered cores or coloured |
Assembly | : | in concentric layers |
Screen | : | (when required) aluminum bonded to polyester tape + tinned copper drain wire |
Jacket (see note) | : | overall PVC type TM1 to BS 7655 |
Test Voltage | : | 1000Vac - 1 min. |
Rated Voltage | : | 300/500 V |
Rated Temperature | : | 70 Degree C |
Min. Insulation Resistance | : | at 200C : 25M Ohm.km |
Max. Mutual Capacitance | : | of adjacent cores at 1kHz : 250 pF/m |
Conductor Resistance | : | refer to technical section |
Note : Optional 90-Degree / 105-Degree / FR / LS0H |
Number of cores | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 10 | 12 | 14 | 16 | 18 | 20 | 21 | 24 | 25 | 27 | 30 | 34 | 37 | 40 | 50 | 61 | 80 |
OD (mm, approx) | 4.9 | 5.1 | 5.5 | 5.9 | 6.3 | 6.3 | 6.6 | 7.3 | 7.8 | 8.3 | 8.7 | 9.1 | 9.5 | 9.7 | 10.3 | 10.4 | 10.8 | 11.3 | 11.9 | 12.3 | 12.7 | 14 | 15.3 | 17.3 |
Kg/Km (approx) | 31 | 37 | 43 | 52 | 60 | 63 | 70 | 84 | 97 | 110 | 123 | 136 | 149 | 155 | 174 | 181 | 193 | 212 | 237 | 255 | 274 | 335 | 402 | 516 |
Item Code for screened : VA7 V -- x 22 AWG K ----- For unscreened : V V - x 22 AWG K ----- (* For Tinned Cu, add 'T' after conductor size)