Specification |
: |
Generally to VDE series 800 |
|
|
|
Conductor |
: |
Flexible copper class 5 to IEC 60228 |
Insulation |
: |
PE type L/MD to BS 7878 |
Identification |
: |
Numbered Pairs or coloured |
Pairing |
: |
Two Insulated conductors twisted together to form a pair |
Screen |
: |
each pair individually screened with Al/Pet foil + tinned copper drain wire(0.5mm2) |
Assembly |
: |
Pairs assembled in concentric layers with overall polyester foil |
Overall Screen |
: |
tinned copper braid 85% coverage |
Jacket |
: |
overall PVC type TM1 to BS 7655 |
Test Voltage |
: |
1000 Vac - 1 min. |
Spark test |
: |
4 KV |
Rated Voltage |
: |
300 V |
Rated Temperature |
: |
700C |
Min.Insulation Resistance |
: |
at 200C : core to core=5G Ohm.km, screen to screen=1M Ohm.km |
Max mutual Capacitance |
: |
at 1 kHz : 115 pF/m |
Conductor Resistance |
: |
refer to technical section |
|