Specification |
: |
BS 7629 - Part 1 |
|
|
|
Conductor |
: |
Solid(Class-1) -or- Stranded(Class-2) copper to BS 6360 |
Insulation |
: |
Cross linked compound type EI2 or GP4 or E15 to BS 7655. When necessary, a fire performant tape may be applied over the conductor or over the insulation. |
|
|
|
Lay-up |
: |
A drain wire shall be run along the lay-up cores |
Screen |
: |
Laminated Aluminum tape bonded to a baking material, helically applied with 25% overlap, the metallic side down. |
Sheath |
: |
LTS 3 compound to BS 7655: Section 6.1 |
Rated Voltage |
: |
300/500 V |
Conductor Resistance |
: |
to BS 6360 |
Spark Test on Insulation |
: |
to BS 5099 |
Voltage Test |
: |
2000 V ac |
|
|
|
Resistance to fire |
: |
to BS 6387 - category C |
Resistance to fire with water |
: |
to BS 6387 - category W |
Resistance to fire with mechanical shock |
: |
to BS 6387 - category Z |
Flame propagation test on single cable |
: |
to BS 4066 - part 1 |
Smoke Emission |
: |
to BS 7622 |
Minimum Transmittance |
: |
80% for cables of diameter <= 20mm 60% for cables of diameter <= 20mm to 40mm |