general@tekab.com.
Thursday, November 21st, 2024
Type | : |
|
||
Specification | : | BS 7629 - Part 2 |
Conductor | : | Solid, Stranded or Flexible Copper to BS 6360 |
Insulation | : | Cross linked compound type EI2 or GP4 or EI5 to BS 7655. When necessary, fire performant tape(s) may be applied over the conductor or over the insulation. |
Pairing | : | The insulated cores are uniformly twisted to form a pair The 2-pair cable shall be assembled as a quad. |
Lay-up | : | The pairs are assembles in concentric layers. If necessary, a tape shall be applied over the assembly. A drain wire shall be run along the assembly. |
Screen | : | Laminated Aluminum tape bonded to a baking material, helically applied with 25% overlap, the metallic side down. |
Inner Sheath | : | Halogen Free LTS 3 compound to BS 7655: Section 6.1 |
Armouring | : | Single layer of Galvanized Steel Wires |
Sheath | : | LTS 3 compound to BS 7655: Section 6.1 |
Rated Voltage | : | 300/500 V |
Conductor Resistance | : | to BS 5099 |
Spark Test on Insulation | : | to BS 5099 |
Voltage Test | : | 2000 V ac |
Area of conductor mm2 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 |
Number of Pairs | 1 | 2 | 5 | 10 | 20 | 1 | 2 | 5 | 10 | 20 | 1 | 2 | 5 | 10 | 20 |
Overall Dia (Max, mm) | 11.7 | 15.9 | 18.8 | 24.0 | 31.0 | 12.7 | 17.6 | 21.0 | 27.0 | 36.0 | 14.9 | 20.0 | 25.0 | 31.4 | 42.0 |
Kg/Km (approx) | 300 | 550 | 750 | 1250 | 1920 | 350 | 650 | 930 | 1550 | 2720 | 520 | 800 | 1350 | 2050 | 3620 |
* Two pairs are assembled as a quad.