Specification | : | BS 6004, IEC 227, VDE 0281 |
Conductor | : | Flexible copper Class-5 to BS 6360 |
Insulation (see note) | : | PVC type TI1 to BS 7655 |
Rated Voltage | : | 450 / 750 V |
Note : Optional 85-Degree / 90-Degree / 105-Degree |
Area of conductor, mm2 | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 |
Overall Dia(Max, mm) | 3.3 | 4.0 | 4.6 | 5.2 | 6.7 | 7.8 | 9.7 | 10.9 | 12.8 | 14.6 | 17.1 | 18.8 | 20.9 | 23.3 | 25.6 | 29.6 | 33.2 | 36.9 |
Kg/Km (approx) | 20 | 33 | 48 | 69 | 115 | 173 | 270 | 360 | 513 | 722 | 997 | 1237 | 1523 | 1908 | 2483 | 3060 | 3600 | 4537 |